The Compact Plug-in Arrestors for Indoor
The compact plug-in indoor use arrestor series protects equipment by absorbing the induced lightning surge that appears in power or signal lines caused by lightning.
Features
- Small plug-in structure.
- The equipment is built so that the line does not open even if the body is pulled from the terminal, so it has excellent maintainability.
- The SR Series complies with JIS standards for power: C5381-1 (2004), and for the signal: C5381-21 (2004).
Specification
Model name | SR-DS | SR-DA | SR-DP | SR-TC | |
---|---|---|---|---|---|
Use | Two-wire system transmitter circuit 4 - 20mA DC signal circuit 1 - 5V DC signal circuit |
100V AD/DC control circuit, contact circuit | Contact signal circuit Pulse signal circuit 24V DC power supply circuit |
Thermocouple circuit mA / mV circuit |
|
Maximum rating value (Line) | Voltage | 52V DC | 150V AC 180V DC |
50V DC | 8V DC |
Current | 100mA DC | 100mA DC | 200mA DC | 50mA DC | |
Voltage protection level | Ground | Below 350V | Below 900V | Below 620V | Below 620V |
Maximum discharge current Between (L-E) 8/20µs |
20kA (single line 10kA) | ||||
Internal resistance between the input terminal | Around 5Ω (single line) |
0Ω | |||
Response speed | 3ns |
Model name | SR-TR | SR-D24 | SR-A100A | SR-A200A | |
---|---|---|---|---|---|
Use | RTD circuit Potentiometer circuit |
DC24V Power circuit |
AC/DC100V Power circuit |
AC200V Power circuit |
|
Maximum rating value (Line) | Voltage | 8V DC | 50V DC | 150V AC/ 180V DC |
255V AC |
Current | 2mA DC | 1A DC | - | - | |
Voltage protection level | Ground | Below 620V | Below 330V | Below 700V | Below 1.4kV |
Maximum discharge current (between L-E) 8/20µs | 10kA (3 lines) | 10kA (Single line 5kA) |
80kA (Single line 40kA) |
||
Internal resistance between the input terminal | 0Ω | ||||
Response speed | 3ns |