HINL200A Series Signal Converters
The HINL 200A Series signal converters receives process signals such as flow rate, pressure, temperature, etc. and converts isolated signals to standardized signals. These highly-reliable signal converters; which have a rich product lineup, can be used in a wide variety of applications.
Features
- Removable plug-in structure
- Does not use an aluminum electrolytic capacitors that has components with limited lifespan.
200A Series
Since it is an isolated 2 output (4 - 20mA DC or 1 - 5V DC, please specify when ordering), it can be used independently or monitoring and control.
Lineup
Model | Product name |
---|---|
200TCA | Thermocouple temperature converter |
200TRA | Resistance temperature detector (RTD) temperature converter |
200MVA | mV converter |
200PRA | Potentiometer converter |
200DLA | Distributor |
200DRA | Distributor (with square root extractor) |
200ICA | Isolator |
200VIA | Voltage-current converter |
Specification
Model | 200TCA | 200TRA | 200MVA | 200PRA |
---|---|---|---|---|
Input signal | JIS Standards Thermocouple R,K,E,J,T,S,B,N |
JIS Standards Resistance temperature detectors (RTD) Pt100Ω |
mV,V,mA | Potentiometer 130-2000Ω |
Output signal | Isolation 2 output: Output 1-5V DC or 4-20mA DC (please specify when ordering) | |||
Allowable load resistance of output signal |
1-5V DC output: above 250kΩ (First output), above 2kΩ (Second output) 4-20mA DC output: below 750Ω (First output) below 350Ω (Second output) |
|||
Conversion accuracy | ±0.4%FS (More than 5mV Span)(Note 1) |
±0.25%FS(Note 1) | ±0.2%FS(Note 1) | ±0.25%FS |
Power supply voltage | 85-132V AC 50/60Hz or 24V DC (please specify when ordering) | |||
Power consumption (VA) (at 100V AC drive) |
3.3 | 3.3 | 3.3 | 3.4 |
Isolation | Interconnection present among Input - First Output - Second output - Power supply | |||
Withstand voltage | Between the ground terminal and power supply terminal: 2000V AC, 1 minute Interconnection among Input / Output / Power supply: 2000V AC, 1 minute Interconnection among output: 1000V AC, 1 minute |
|||
Insulation resistance | Between each terminal and ground terminal: 100MΩ / 500V DC | |||
Structure | Flat-type plug-in structure (socket: Dedicated 11-pin socket, screw terminal M3) | |||
Installation method | DIN rail or wall mounting compatible | |||
Weight | Equipment: Approx. 220g Socket: Approx.80g | |||
Function changeover switch | - | - | - | - |
Model | 200DLA | 200DRA | 200ICA | 200VIA |
---|---|---|---|---|
Input signal | Two-wire system transmitter (nominal DC24V) | Output 1 - 5V DC or 4 - 20mA DC (please specify when ordering) |
Various voltage and current signals | |
Output signal | Isolation 2 output: Output 1 - 5V DC or 4 - 20mA DC(please specify when ordering) | |||
Allowable load resistance of output signal |
1 - 5V DC output: above 250kΩ (First output), above 2kΩ (Second output) 4 - 20mA DC output: below 750Ω (First output) below 350 (Second output) |
|||
Conversion accuracy | ±0.2%FS | ±0.3%FS | ±0.2%FS | ±0.2%FS(Note 1) |
Power supply voltage | 85 - 132V DC 50/60Hz or 24V DC (please specify when ordering) | |||
Power consumption (VA) (at 100V AC drive) |
4.2 | 4.2 | 3.3 | 3.3 |
Isolation | Interconnection present among Input - First Output - Second output - Power supply | |||
Withstand voltage | Between the ground terminal and power supply terminal: 2000V AC, 1 minute Interconnection among Input / Output / Power supply: 2000V AC, 1 minute Interconnection among output: 1000V AC, 1 minute |
|||
Insulation resistance | Between each terminal and ground terminal: 100MΩ / 500V DC | |||
Installation method | DIN rail or wall mounting compatible | |||
Weight | Equipment: Approx. 220g Socket: Approx. 80g | |||
Function changeover switch | Transmitter power ON/OFF |
Transmitter power ON/OFF |
- | - |
Note 1 The accuracy changes depending on the range and the input specifications, please refer to the CS sheet.