HINL200A Series Signal Converters

HINL200A Series Signal Converters

The HINL 200A Series signal converters receives process signals such as flow rate, pressure, temperature, etc. and converts isolated signals to standardized signals. These highly-reliable signal converters; which have a rich product lineup, can be used in a wide variety of applications.

Features

  • Removable plug-in structure
  • Does not use an aluminum electrolytic capacitors that has components with limited lifespan.

200A Series

Since it is an isolated 2 output (4 - 20mA DC or 1 - 5V DC, please specify when ordering), it can be used independently or monitoring and control.

Lineup

HINL200A Series Signal Converters Product Lineup
ModelProduct name
200TCA Thermocouple temperature converter
200TRA Resistance temperature detector (RTD) temperature converter
200MVA mV converter
200PRA Potentiometer converter
200DLA Distributor
200DRA Distributor (with square root extractor)
200ICA Isolator
200VIA Voltage-current converter

Specification

HINL 200A Series Signal Converters Product Specification -1
Model200TCA200TRA200MVA200PRA
Input signal JIS Standards Thermocouple
R,K,E,J,T,S,B,N
JIS Standards Resistance temperature detectors (RTD)
Pt100Ω
mV,V,mA Potentiometer
130-2000Ω
Output signal Isolation 2 output: Output 1-5V DC or 4-20mA DC (please specify when ordering)
Allowable load
resistance of output signal
1-5V DC output: above 250kΩ (First output), above 2kΩ (Second output)
4-20mA DC output: below 750Ω (First output) below 350Ω (Second output)
Conversion accuracy ±0.4%FS
(More than 5mV Span)(Note 1)
±0.25%FS(Note 1) ±0.2%FS(Note 1) ±0.25%FS
Power supply voltage 85-132V AC 50/60Hz or 24V DC (please specify when ordering)
Power consumption (VA)
(at 100V AC drive)
3.3 3.3 3.3 3.4
Isolation Interconnection present among Input - First Output - Second output - Power supply
Withstand voltage Between the ground terminal and power supply terminal: 2000V AC, 1 minute
Interconnection among Input / Output / Power supply: 2000V AC, 1 minute
Interconnection among output: 1000V AC, 1 minute
Insulation resistance Between each terminal and ground terminal: 100MΩ / 500V DC
Structure Flat-type plug-in structure (socket: Dedicated 11-pin socket, screw terminal M3)
Installation method DIN rail or wall mounting compatible
Weight Equipment: Approx. 220g Socket: Approx.80g
Function changeover switch - - - -
HINL200A Series Signal Converters Product Specifications-2
Model200DLA200DRA200ICA200VIA
Input signal Two-wire system transmitter (nominal DC24V) Output 1 - 5V DC or 4 -
20mA DC (please
specify when ordering)
Various voltage and current signals
Output signal Isolation 2 output: Output 1 - 5V DC or 4 - 20mA DC(please specify when ordering)
Allowable load
resistance of output signal
1 - 5V DC output: above 250kΩ (First output), above 2kΩ (Second output)
4 - 20mA DC output: below 750Ω (First output) below 350 (Second output)
Conversion accuracy ±0.2%FS ±0.3%FS ±0.2%FS ±0.2%FS(Note 1)
Power supply voltage 85 - 132V DC 50/60Hz or 24V DC (please specify when ordering)
Power consumption (VA)
(at 100V AC drive)
4.2 4.2 3.3 3.3
Isolation Interconnection present among Input - First Output - Second output - Power supply
Withstand voltage Between the ground terminal and power supply terminal: 2000V AC, 1 minute
Interconnection among Input / Output / Power supply: 2000V AC, 1 minute
Interconnection among output: 1000V AC, 1 minute
Insulation resistance Between each terminal and ground terminal: 100MΩ / 500V DC
Installation method DIN rail or wall mounting compatible
Weight Equipment: Approx. 220g Socket: Approx. 80g
Function changeover switch Transmitter power
ON/OFF
Transmitter power
ON/OFF
- -

Note 1 The accuracy changes depending on the range and the input specifications, please refer to the CS sheet.