Skip to main content

Hitachi High-Tech
  1. Home
  2. Products & Services
  3. Instruments & Control Systems Related Solutions
  4. Panel Instruments
  5. HINL250A Series Signal Converters

HINL250A Series Signal Converters

HINL250A Series Signal Converters

The HINL 250A Series signal converters come with standard functions such as burnout functions, square root extraction operation, and other functions while having a compact body with a width of 26mm (about half of the HINL200 series).

Features

  • Electrical current with isolation, 2 output is possible (4 - 20mA DC × 2)
  • Can be installed by attaching
    Spacer is not needed, high-density mounting is possible.

Lineup

HINL 250A Series Signal Converters Product Lineup
ModelProduct name
250TCA Thermocouple temperature converter
250TRA Resistance temperature detector (RTD) temperature converter
250MVA mV converter
250PRA Potentiometer converter
250DLA Distributor
250DRA Distributor (with square root extractor)
250ICA Isolator
250VIA Voltage-current converter

Specification

HINL 250 A Series Signal Converters Product Specification-1
Model250TCA250TRA250MVA250PRA
Input signal JIS Standards
Thermocouple
R,K,E,J,
T,S,B,N
JIS Standards
Resistance temperature detectors (RTD)
Pt100
mV,V,mA Potentiometer
130-2000Ω
Output signal Isolation 2 output: Output 1-5V DC or 4-20mA DC (please specify when ordering)
Allowable load
resistance of output signal
1-5V DC output: above 2kΩ (First and second output have both the same specifications)
4-20mA DC output: below 750Ω (First output) below 350 (Second output)
Conversion accuracy ±0.4%FS(Note 1)
(More than 5mV span)
Zero transition less than 50%
±0.25%FS
(More than 50°C span)
(Note 1)
±0.2%FS(Note 1) ±0.25%FS
Power supply voltage 85-132V AC 50/60Hz or 24V DC (please specify when ordering)
Power consumption(VA)
(at 100V AC drive)
3.3 3.3 3.3 3.4
Isolation Interconnection present among Input - First Output - Second output - Power supply
Withstand voltage Between the ground terminal and power supply terminal: 2000V AC, 1 minute
Interconnection among Input / Output / Power supply: 2000V AC, 1 minute
Interconnection among output: 1000V AC, 1 minute
Insulation resistance Between each terminal and ground terminal: 100MΩ / 500V DC
Structure Flat-type plug-in structure (socket: Dedicated 11-pin socket, screw terminal M3)
Installation method DIN rail or wall mounting compatible
Weight Equipment: Approx. 150g Socket: Approx.30g
Function changeover switch - - - -

Note 1 The accuracy changes depending on the range and the input specifications, please refer to the CS sheet.

HINL 250 A Series Signal Converters Product Specification-2
Model250DLA250DRA250ICA250VIA
Input signal JIS Standards
Thermocouple
R,K,E,J,T,S,B,N
JIS Standards
Resistance temperature detectors (RTD)
Pt100
mV,V,mA Potentiometer 130-2000Ω
Output signal Isolation 2 output: Output 1-5V DC or 4-20mA DC (please specify when ordering)
Allowable load
resistance of output signal
1-5V DC output: above 2kΩ (First and second output have both the same specifications)
4-20mA DC output: below 750Ω (First output) below 350 (Second output)
Conversion accuracy ±0.2%FS ±0.3%FS
(Output 0% and
10-100%)(Note 1)
±0.2%FS ±0.2%FS
(More than 5mV span)
Zero transition less than 50%
Power supply voltage 85-132V AC 50/60Hz or 24V DC (please specify when ordering)
Power consumption(VA)
(at 100V AC drive)
4.2 4.2 3.3 3.3
Isolation Interconnection present among Input - First Output - Second output - Power supply
Withstand voltage Between the ground terminal and power supply terminal: 2000V AC, 1 minute
Interconnection among Input / Output / Power supply: 2000V AC, 1 minute
Interconnection among output: 1000V AC, 1 minute
Insulation resistance Between each terminal and ground terminal: 100MΩ / 500V DC
Structure Flat-type plug-in structure (socket: Dedicated 11-pin socket, screw terminal M3)
Installation method DIN rail or wall mounting compatible
Weight Equipment: Approx.150g Socket: Approx.30g
Function changeover switch Transmitter power : can be changed by the ON / OFF (short metal fixture) Transmitter power : can be changed by the ON / OFF (short metal fixture) - -

Note 1 The accuracy changes depending on the range and the input specifications, please refer to the CS sheet.

Contact Us